Interpretation #6557

Published July 01, 2010

Original Request

Code Version
2007
Code
RESIDENT
Code Description
Residential
Chapter
41
Section
4101.17.1.6
Topic
Barriers

Question

Is it the intent of Florida Building Code - Residential Section R4101.17.1.6 to consider a 2 3/8" chain link fence mesh opening to be within acceptable construction tolerances?

Answer Published 07/01/2010 at 8:21 PM

No. Florida Building Code - Residential Section R4101.17.1.6
specifically calls for a maximum mesh size of 2 1/4".

Commentary

Construction tolerances are for variations in field conditions typical in construction and NOT for conditions which are controllable at a manufacturing plant. A commission report prepared by National Institute of Health also addressed this issue. It noted that “standard chain link fencing… would allow most children ages 24 – 42 months to place their feet fully inside the openings. This design characteristic may account for reports of young children who drowned after scaling chain link fences of heights up to 6 ft”. This issue also came up during the ICC 2006 proposed code changes. The National Drowning Prevention Alliance filed a proposal to reduce the opening size to 1.25”; it was defeated and the MAXIMUM 2-1/4" mesh dimension was retained.