Interpretation #8563

Original Request

  • Requested By: Donald Naylor
  • Requester E-Mail: Donald407@cfl.rr.com
  • Code Version: 2021
  • Code: ENERGY
  • Code Description:
  • Chapter:
  • Section: 408.2.2.1
  • Topic: Test and balance requirements

  • Question: Is the intent of Section C408.2.2.1's requirement that test and balance procedures be "in accordance with NEBB" to be interpreted to require Certified NEBB T&B reporting on projects under 5000sf or fall under either or both of the exceptions for certified T & B reports according to section C408.2.2.

Answer:

No, the building in question is under 5,000sf and not required to comply under C408.
C408.2.2 Air distribution system testing, adjusting and balancing. Construction documents shall require that a written balance report be provided to the owner or the designated representative of the building owner for HVAC systems serving zones with a total conditioned area exceeding 5000 square feet (465 m2). Air distribution systems shall be tested, adjusted and balanced by a licensed engineer or a company or individual holding a current certification from a recognized testing and balancing agency
organization in accordance with generally accepted engineering standards.

Commentary:

None.