Interpretation #8549

Original Request

  • Requested By: Samuel Cassity
  • Requester E-Mail: Sam@ZAArch.com
  • Code Version: 2021
  • Code: ENERGY
  • Code Description:
  • Chapter:
  • Section: TABLE C402.1.3
  • Topic: CLIMATE ZONE 2, ALL OTHER, MASS, R-5.7ci, Note c

  • Question: Does a typical CMU building with #5 rebar at 4'-0" o.c. maximum in solid concrete fill and 16" deep bond beam at top of an 8'-0" wall qualify as a MASS Building?

Answer:

This would be up to the designer to provide the calculations on this wall.

Commentary:

It could be a mass wall for energy purposes. While the commercial section of the FBC-EC does not define mass walls, the residential portion does have a definition. The code permits the use of definitions from other volumes of the code when a term is not defined in the volume in question.