Interpretation #8548
Original Request
-
Requested By:
Stephen Poposki
-
Requester E-Mail:
spoposki@capecoral.net
-
Code Version:
2021
-
Code:
NEC
-
Code Description:
-
Chapter:
-
Section:
210.52(E)
-
Topic:
Required outdoor receptacles in relation to screened enclosures
-
Question:
Is it the intent of section 210.52(E) of the 2017 NEC to require two outdoor receptacle outlets (one on the outside of a screened porch or lanai and one on the inside of a screened porch or lanai) at the rear of a single family dwelling where the lanai is enclosed by a screened enclosure? [This question is posed due to concern that flexible cords may be used through a door of the screened enclosure in the future.]
Commentary:
The NEC handbook shows a nice description of this. It shows an outlet on a porch or deck that may also be used for the required outlet at the back of the house. However, if it is a screened porch or lanai, in order to use that outlet for the required backyard receptacle, the cord would have to be run through a wall or a doorway. Running a cord through a doorway is prohibited by NEC 400.12. You are not allowed to violate one code article to satisfier another one.
|
|
|