Section 704.2 prohibits any reduction in pipe size in the direction of flow, except for water closet bend fittings and water closet flanges. There is no such exception given for grease interceptor connections. Although grease interceptors are equipped with flow control devices that essentially restrict the flow entering the interceptor, this does not relieve the installer of the responsibility of complying with 704.2.