If the building is considered a "renovated building" defined as; estimated costs exceed 30% of assessed value of the structure, (see R101.4.2 and Definitions in chapter 2) then the replacement fenestration products need to meet a maximum SHGC of .25 and a maximum U factor of .40 for a building in climate zone 2 (see Table 402.1.2 note a.) if it is an existing building and not considered a renovated building then it is exempt from the provisions of the Energy Code