#1. No. Read 250.92 (B) the last sentence which states "Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a
mechanical connection of the raceway(s)."
#2. If this is a service raceway, meaning it is before the means of overcurrent on the premises, yes.
#3. Yes