No. 903.2.8 and 903.2.8.1 state that all R-3's are required to be fire sprinkler protected. A SFD is an R-3. If one constructs an R-3, in accordance with the FBC-Building, it is required to be fire sprinkler protected regardless of size. The 903.2.11.3 Exception 1, is only an exception to the three story and above fire sprinkler requirement from Florida Statute 553.895 (2). Now, if the SFD is constructed in accordance with the FBC-R and is three stories or less in height, then no fire sprinklers would be required as the FBC-R does not have a similar requirement to 903.8 or 903.8.1.