Chapter:
Chapter 30-Elevators and Conveying Systems
Section:
3005.2
Topic:
Fire Command Centers and Elevator Control Rooms
Question:
Per FBC 2017 Section 3005.2 – Is the Fire Command Center of a High-rise building considered an elevator control/machine room and as such is it required to be ventilated or air-conditioned?
Answer:
No, although normal light and ventilation requirements apply.