Interpretations Request Input

Original Request

  • Request ID: 8838
  • Requested By: Carlos Dennis
  • Requester E-Mail: carlos.dennis@leesburgflorida.gov
  • Code Version: 2021
  • Code: FUELGAS
  • Code Description:
  • Chapter:
  • Section: 403.4
  • Topic: galvanized piping material
  • Question: Is galvanized piping material allowed to be used for above ground gas piping work
  • Comment: None

Existing Interpretations and/or Declaratory Statements Related to this request

Input Received:

Yes it is allowed. There are no restriction on the use of galvanized pipe for natural gas piping systems in the Florida Fuel Gas Code or the Florida Residential Code.
Agree
404.11.1 galvanizing does not deem zinc coating as adequate protection for underground gas piping. Although I also could not find language for galvanized piping above ground, I would question 403.3 other materials as to whether it needs to be investigated and tested that it is safe and suitable for the proposed use and that it is recommended by the manufacturer for that service and approved by the code official.
I agree that galvanized piping can be used above ground for a gas piping.

Answer:

Yes, it is allowed with the caveat that it must suitable for the environment where it is located.

Commentary:

Please refer to Section 404.11.1 where the code indicates galvanizing does not deem zinc coating as adequate protection for underground gas piping. In any case, it needs to be investigated and tested that it is safe and suitable for the proposed use and that it is recommended by the manufacturer for that service and approved by the code official.

Comments on Draft:

I agree with the draft answer
I concur
Agree