Question:
Is it the intent of the exemption in section 706.1 that Reroofing shall not be required to meet the minimum design slope requirement of one-quarter unit vertical in 12 units horizontal for roofs that provide positive roof drainage within 48 hours of precipitation?
Comment:
Chapter 2 definitions-
POSITIVE ROOF DRAINAGE. The drainage condition in which consideration has been made for all loading deflections of the roof deck, and additional slope has been provided to ensure drainage of the roof within 48 hours of precipitation.
Existing Interpretations and/or Declaratory Statements Related to this request
Input Received:
Yes: FBC-Existing Section 706.1 including the Exception states that reroofing shall not be required to meet the minimum design slope requirement of one-quarter unit vertical in 12 units horizontal (2% slope) for roofs that provide positive roof drainage. This section is silent regarding reroofing on roofs that do not provide positive drainage. The section should not be read to connotate that positive roof drainage is required, or that reroofing on a roof that does not provide positive roof drainage is prohibited.
Agree
agree
Answer:
Yes: FBC-Existing Section 706.1 including the Exception states that reroofing shall not be required to meet the minimum design slope requirement of one-quarter unit vertical in 12 units horizontal (2% slope) for roofs that provide positive roof drainage. This section is silent regarding reroofing on roofs that do not provide positive drainage. The section should not be read to connotate that positive roof drainage is required, or that reroofing on a roof that does not provide positive roof drainage is prohibited.
Commentary:
None.
Comments on Draft:
agree
Agree.
Note the specific text - for roofs that provide positive roof drainage. But concur with the rest of the commentary.