No, automatic smoke detection shall be provided for any Group H occupancy for highly toxic gases, organic peroxides and oxidizers
I agree with Michael Grimm, this could apply to any of the H group.
I think you need to read the question. He asks if it applies to H-5 or occupancies used for the manufacture of organic coatings. If an H-1, H-2, H-3, or H-4 is manufacturing organic coating, then an automatic smoke detection system is required, An H1 through H-4 not manufacturing organic coatings would not be required to have a smoke detection system by the terms of Section 907.2.5.