Contact Us   |   Sign In   |   Register

Log in

Interpretations Request Input

Original Request

  • Request ID: 8563
  • Requested By: Donald Naylor
  • Requester E-Mail: Donald407@cfl.rr.com
  • Code Version: 2021
  • Code: ENERGY
  • Code Description:
  • Chapter:
  • Section: 408.2.2.1
  • Topic: Test and balance requirements
  • Question: Is the intent of Section C408.2.2.1's requirement that test and balance procedures be "in accordance with NEBB" to be interpreted to require Certified NEBB T&B reporting on projects under 5000sf or fall under either or both of the exceptions for certified T & B reports according to section C408.2.2.
  • Comment: There is a commercial gas station project with 3500 total SF with two 12ton AC units. An inspector is requiring a NEBB certified report based on interpretation that C408.2.2.1's requirement for the T&B to be "In accordance with NEBB" means following all points of NEBB including the certification and equipment calibration requirements. Comment provided at the inspection is in quotes below. "Within their section 2.4 NEBB requires the document to have NEBB seal/stamp affixed. It requires the instrumentation page to be included (procedures are found in section 4). These elements are missing from the report on site. As such, the report does not meet the requirements of the FBC-EC." It is my understanding and experience that the report is not required to be NEBB certified based on the exceptions provided in C408.2.2 that the report should include a statement affirming that the NEBB procedures for testing and balancing were followed. These procedures being found in Part 2 of the NEBB manual.

Existing Interpretations and/or Declaratory Statements Related to this request

Input Received:

A few comments here. First, I don't think the inspector has the authority to require or judge the report. C408.2.2 states that the balance report be provided to the owner or owner's rep, doesn't say anything about providing one to the building dept. Second, if I'm out voted on part one, in my opinion the statement "in accordance with" is vague enough that it leaves it up to the Building Official to make the call.
NO, the building in question is under 5,000sf and not required to comply under C408.
C408.2.2 Air distribution system testing, adjusting and balancing. Construction documents shall require that a written balance report be provided to the owner or the designated representative of the building owner for HVAC systems serving zones with a total conditioned area exceeding 5000 square feet (465 m2). Air distribution systems shall be tested, adjusted and balanced by a licensed engineer or a company or individual holding a current certification from a recognized testing and balancing agency
organization in accordance with generally accepted engineering standards.
Exceptions:
1. Buildings with cooling or heating system capacities of 15 tons or less per system may be tested and balanced by a mechanical contractor licensed to design and install such system(s).
2. Buildings with cooling or heating system capacities of 65,000 Btu/h or less per system are exempt
from the requirements of this section

Answer:

No, the building in question is under 5,000sf and not required to comply under C408. C408.2.2 Air distribution system testing, adjusting and balancing. Construction documents shall require that a written balance report be provided to the owner or the designated representative of the building owner for HVAC systems serving zones with a total conditioned area exceeding 5000 square feet (465 m2). Air distribution systems shall be tested, adjusted and balanced by a licensed engineer or a company or individual holding a current certification from a recognized testing and balancing agency organization in accordance with generally accepted engineering standards.

Commentary:

None.

Comments on Draft:

agree
agree
agree