Question:
Is it the intent of the definition of addition to use FLOOR AREA, GROSS or FLOOR AREA, NET as defined in the Florida Building Code, Building ?
Comment:
For example: Would enclosing a carport or changing a garage into living area, in a single family residence be considered an Addition or an alteration?
Existing Interpretations and/or Declaratory Statements Related to this request
Is it the intent of FRC 5th edition definition of habitable space to include a Florida Room as a non-habitable room and therefore creating a change of use when a Florida Room is converted into a living room by virtue of removing or not removing the door that leads to the Florida room?
1. Is the definition of ""Substantial Improvement"" applicable throughout the Code or only in the section that specifically uses this term? Chapter 5, Section 505.1 it states ""Level 3 alterations apply where the work area exceeds 50 percent of the aggregate area of the building."" this appears to be different than the definition of substantial improvement. Based on this, can it be stated the 50% threshold is based on aggregate area and not dollars? 2. Additionally, please clarify the definition of ""VALUE"" as it permits replacement cost vs market value indicated within Substantial Improvement definition. Are they interchangeable or both acceptable?
If the ""north"" facing facets comprise more than 25% of the roof area, is it the intent of the Roof Section definition, to require full replacement of the roof even if only the ""north"" facing facets of a roof are damaged in a storm, and the remaining East, West, and South facing facets remain intact and in good condition?
Is it the intent of a. From definition #2, a component or group of components which supports more than 30% of the total area of the structures roof or floor i. Does total refer to the sum of all roof or floor areas throughout the entire structure, or for the roof section as defined by Chapter 2? ii. If a 20x50= 1,000SF one-story building has fire walls which section the building into five, 20 long x 10 wide office spaces, would fire damage to the roof of one office space (20 x 10 = 200 SF) be considered as 20% of the total building area and therefore would not be considered as substantial damage OR would each office space be considered its own roof area, with 100% (>30%) of the roof (200 SF) considered as damaged, and require analysis of if the roof had been reduced per the remainder of the definition? b. From definition #2, the remaining capacity of such affected elements, with respect to all dead and live loads, is less than 75 percent of that required by this code for new buildings of similar structure, purpose and location. i. If the damaged vertical component(s) have been reduced by more than 20% of its predamage condition, is it appropriate to only load Dead and Live load onto the remainder (undamaged) cross-section, and exclude wind, seismic, etc? ii. Is it acceptable for the remainder (undamaged) cross-section to have less capacity than required by the current code Live and Dead load (exclude wind, seismic, etc), as long as it has more than 75% of the required capacity? For instance, a beam with a capacity of 76 k*in is acceptable to resist an applied Moment of 100 k*in.
Input Received:
Addition.
Yes, however, Goss and net is really used within Chapter 10, FBC-Bldg to assist in occupancy loading. Saying that, if something is not defined within one volume of a code, then go to the prime (Bldg) to see if it is defined.
Look first at the definition of Area, Bldg - the last sentence reads "areas of the building not provided with surrounding walls shall be included in the building area if such areas are included within the horizontal projection of the roof or floor above." The definition of Floor Area, gross has similar verbiage.
In the FBC-Existing, Section 603.1 scope of a Level II Alteration includes the reconfiguration of space,......, the reconfiguration or extension of any system, ...... In enclosing a carport or a garage, that would be extending a wall system within existing floor space due to the roof system being there.
So I would consider this an alteration with a space use change. Be aware of the other code requirements bringing this area into a habitable use.
Addition with Linda's comment.
Answer:
Yes, that is an addition, however, gross and net is really used within Chapter 10, FBC-Bldg to assist in occupancy loading. Saying that, if something is not defined within one volume of a code, then go to the prime (Bldg) to see if it is defined.
Look first at the definition of Area, Bldg - the last sentence reads "areas of the building not provided with surrounding walls shall be included in the building area if such areas are included within the horizontal projection of the roof or floor above." The definition of Floor Area, gross has similar verbiage.
In the FBC-Existing, Section 603.1 scope of a Level II Alteration includes the reconfiguration of space,......, the reconfiguration or extension of any system, ...... In enclosing a carport or a garage, that would be extending a wall system within the existing floor space due to the roof system being there.
This an alteration creating additional habitable space, therefore, an addition. Be aware of the other code requirements bringing this area into a habitable use.
Commentary:
None.
Comments on Draft:
This is an addition because you are increasing the enclosed habitable area of the structure.
I agree with the draft interpretation
To me, the carport is an accessory utility structure being converted and would be a change of occupancy. From FBC Existing, part of the definition of “Change of Occupancy” 3. "Any change in use within a group for which there is a change in the application of the requirements of this code".
Also “carport” is listed under Group U occupancy per FBC Bldg 312.1
Converting un-conditioned, non-habitable space into conditioned, habitable space is an addition. It is always included in Area Calculations block on Cover sheets, just goes into a different column/section now, IMHO. And other Code requirements kick in.... Energy, etc. Sorry so late with this, Doug. Routed to Junk folder for some reason.