I think R704.2.1 is specific to vinyl,
aluminum soffits will still need to show how they meet the wind loads of Tables 301.2(2) and 301.2(3) per R704.1
The 2021 IRC has a sentence in the soffit section "soffit materials not addressed in section...shall be in accordance with the manufacturer's installation instructions" Unfortunately the FBC, Residential does NOT have this sentence. The FBC, Residential section 704.2 does not address aluminum soffit design. Section 704.2.1 only covers vinyl. I was on the committee that drafted the vinyl soffit language and detail, it was exclusive to vinyl soffits.
I agree.. I also think we need to mark this as another area to be update for use of other materials..
I agree.. I also think we need to mark this as another area to be update for use of other materials..
Agree. When we put the soffit section together in the FBC-B we required all manufactured soffit to have product approval. Not putting that requirement in the FBC-R was an oversight.