Yes
607.3.1 requires the damper to be tested and listed for use in dynamic systems where air flow may continue to move.
No.
2020 FMC, 607.3.1 deals with Damper testing. Ceiling radiation dampers shall comply with the requirements of UL 555C or shall be tested as part of a fire-resistance-rated floor/ceiling of roof/ceiling assembly in accordance with ASTM E119.
2020 FMC, 607.6.2.1 deals with Ceiling radiation dampers. Ceiling radiation dampers shall be installed in accordance with the details listed in the fire-resistance-rated assembly and the manufacturer’s installation instructions and the listing.
UL 555C applies to ceiling dampers and ceiling air diffusers intended for use in HVAC systems where the airflow is operational at the time of a fire. Static ceiling radiation dampers are installed only in systems that are not designed to operate during a fire.
This is not a true code interpretation as it is a design question. Saying that and researching, I agree with Pedro’s response. I would clarify it with the statement that the designer needs to determine actual intent of the radiant damper’s use. Each type, static or dynamic, is tested for that specific air flow use.
This is not a true code interpretation as it is a design question. Saying that and researching, I agree with Pedro’s response. I would clarify it with the statement that the designer needs to determine actual intent of the radiant damper’s use. Each type, static or dynamic, is tested for that specific air flow use.
I agree with Pete's analysis.