  • Question: 903.2.11.3 states building over 3 stories must be fire sprinkled. EXCEPTION 1: single and 2 family homes. Does this mean you can build 1&2 family homes 4 story in height using standard construction lumbers without using fire sprinklers or making the ground floor non-combustible?
  • Comment: None

Existing Interpretations and/or Declaratory Statements Related to this request

Input Received:

No. 903.2.8 and 903.2.8.1 state that all R-3's are required to be fire sprinkler protected. A SFD is an R-3. If one constructs an R-3, in accordance with the FBC-Building, it is required to be fire sprinkler protected regardless of size. The 903.2.11.3 Exception 1, is only an exception to the three story an above fire sprinkler requirement from Florida Statute 553.895 (2). Now, if the SFD is constructed in accordance with the FBC-R and is three stories or less in height, then no fire sprinklers would be required as the FBC-R does not have a similar requirement to 903.8 or 903.8.1.
Agree, I think Tony has covered it all.
Doesn't Tony mean that if the 1 and 2 family home is build under the FBC-R it can be any number of stories, not just 3 or less, and doesn't require a sprinkler.
Please disregard my comment, I think I was sleeping. FBC-R is only for up to 3 stories.

Answer:

No. 903.2.8 and 903.2.8.1 state that all R-3's are required to be fire sprinkler protected. A SFD is an R-3. If one constructs an R-3, in accordance with the FBC-Building, it is required to be fire sprinkler protected regardless of size. The 903.2.11.3 Exception 1, is only an exception to the three story and above fire sprinkler requirement from Florida Statute 553.895 (2). Now, if the SFD is constructed in accordance with the FBC-R and is three stories or less in height, then no fire sprinklers would be required as the FBC-R does not have a similar requirement to 903.8 or 903.8.1.

Commentary:

None.

Comments on Draft:

Looks good
I agree. In the third sentence it should read ..."three story and above..." The 903.2.11.3 Exception 1, is only an exception to the three story an above fire sprinkler requirement from Florida Statute 553.895 (2).
Agree with response and Linda's comment
Agree
Looks good. Agree with Linda on the typo.
Whoops, agree with Joe on the typo.
agree with those above.